Features

On line double conversion
1/1High input factor 0.99
High output factor at 0.8
Support the frequency converter Mode
Parallelable up to 4 units
Build–in ECO mode

LCD display

 


Model 1000 - 2000 - 3000 VA
Input Features Input/Output Voltage (Vac) 1 ph + N 220 to 240
Input Voltage Range (Vac) From 176 to 260 (1 ph)
Input Frequency (Hz) 50 - 60 +/- 20%
Input P.F. Better than 0.95
Input Current Distortion (THD) Better than 10%
Maximum Charging Current (Adc) 2 A
Number of cells 3 (1 kVA) - 8 (2-3 kVA)
Input Short Protection Circuit Breaker
Output Features Start on Battery
Yes
Efficiency at 100%load
From 85 to 88%
Output Voltage (Vac)
220 to 240 selectable by software
Output Harmonic Distorsion
< 3% linear load or
< 6% non linear load
Crest Factor
Better than 3 : 1
Voltage Tolerances
< 1% Static load
< 2% Dynamic 50% load step
< 4% Dynamic 100% load step
Waveform Distortion
< 3% Linear load
< 5% Non linear load
Short Circuit Current
150 % nominal current
Voltage Transient Recovery Time
< 10 ms RMS
Wave Form
Sinusoidal
Overload Capabilities
124% for 10 seconds
105% for 10 minutes
Weight w batteries (Kg) 15 (1kVA) - 34-35 (2-3 kVA)
Dimensions L x W x H (mm) 160x400x220 (1kVA) - 200x450x352 (2-3kVA)
Protection IP20
Audible noise level
(1 mt. dBA)
<45
Operating Environment (°) From 0° to 40° C
Humidity (%) < 95 % (non-condensing)

 

 
 

from 500 to 2000 VA

from 1 to 3 KVA
from 1 to 3 KVA in rack 19"
from 6 to 15 KVA 1/1
from 5 to 10KVA 1/1 rack 19"
from 6 to 15 KVA 3/1
from 10 to 160 KVA 3/3
from 10 to 300 KVA 3/3

 

DGtower: download technical data in pdf format (500 k)

DGtower: download user's manual in pdf format (3100 k)

DGtower: download the statement of compliance in pdf format (64 k)

SYSCONV SRL - zona industriale AZZIDA - 33049 San Pietro al Natisone (UD)
Tel. +39 0432 727945 - Fax +39 0432 717605 - Copyright © 2005 SYSCONV s.r.l.  All rights reserved.